Mecer 10000VA/8000W (10kva) UPS ACCESSORY AS THE BELOW W/ 12V9AH BATTERY*16PCS W/ RS232 PORT, W/ RS232 CABLE,w/USB port, w/SNMP slot,w/Usb CABLE W/ terminal block W/ CD ROM
MODEL: ME-10000-WPTU PHASE: Single phase with ground CAPACITY: 10000VA / 8000W
(with AVR, Monitoring Software + Cable & Built-in Surge Protection) – Black
INPUT
Voltage Range Low Line Transfer: 176 VAC ± 3% @ 100% load, 110 VAC ± 3% @ 50% load Low Line Comeback: 186 VAC ± 3% @ 100% load, 120 VAC ± 3% @ 50% load High Line Transfer: 300 VAC ± 3% High Line Comeback: 290 VAC ± 3% Frequency Range: 46~54 Hz or 56~64 Hz Power Factor: ≧ 0.99 @ 100%load
OUTPUT
Output Voltage: 208/220/230/240 VAC AC Voltage Regulation (Batt. Mode): ± 1% Frequency Range (Synchronized Range): 46~54 Hz or 56~64 Hz Frequency Range (Batt. Mode): 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz Current Crest Ratio: 3:1
Transfer Time AC Mode to Batt. Mode: Zero Inverter to Bypass: Zero Waveform (Batt. Mode): Pure Sinewave Harmonic Distortion: ≦ 3 % THD (Linear Load), ≦ 5 % THD (Non-linear Load)
Mecer 10000VA/8000W (10kva) UPS
EFFICIENCY AC Mode: 93% Battery Mode: 91%
BATTERY Battery Type: 12 V / 9 Ah Numbers: 16 Typical Recharge Time: 9 hours recover to 90% capacity Charging Current (max.): 1.0 A / 2.0 A (adjustable) Charging Voltage: 218.4 VDC ±1%
INDICATORS LCD Panel: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM Battery Mode: Sounding every 4 seconds Low Battery: Sounding every second Overload: Sounding twice every second Fault: Continuously sounding
PHYSICAL Dimension, D x W x H (mm): 442 x 190 x 688 Net Weight (kgs): 66
ENVIRONMENT Humidity: 0-95 % RH @ 0- 40°C (non-condensing) Noise Level: Less than 58dB @ 1 Meter
MANAGEMENT Smart RS-232/USB: Supports Windows 2000/2003/XP/Vista/ 2008, Windows 7/8, Linux, Unix, and MAC Optional SNMP: Power management from SNMP manager and web browser
NOTE 1: Derate to 80% of capacity in CVCF mode or when the output voltage is adjusted to 200/208VAC. NOTE 2: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.