See DetailsKey Features
- Output power capacity (VA): 2200 VA
- Output power capacity (Watts): 1980 W
- Nominal input voltage: 160 - 286 V
- Output voltage note: 220/230/240
- Nominal output voltage: 230 V
Features
- StruxureWare Central compatible Enables centralized management via StruxureWare Central.
- High online efficiency Reduces utlility costs, generates less heat.
- Green mode Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
- Energy meter Provides actual kilowatt hours of usage for energy conscious users.
- Predictive replace battery date Dynamically provides the month and year when battery replacement is recommended to aide in long term maintenance planning.
- Intuitive LCD interface Provides clear and accurate information in multiple languages with the ability to configure the UPS locally with easy to use navigation keys.
- Single switched outlet group Single outlet group that may be controlled separately from the UPS for discrete reboot of hung devices, sequenced on/off and non-critical load shedding.
- Pure sine wave output on battery Simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.
- Sequenced network shutdown and reboot Customize network shutdown and reboot sequence of connected servers and UPSs.
- Cold-start capable Provides temporary battery power when the utility power is out.
- SmartSlot Customize UPS capabilities with management cards.
- Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
Smart-UPS Features & Benefits
Availability
- Boost and Trim Automatic Voltage Regulation (AVR) Gives higher application availability by correcting low and high voltage conditions without using the battery (not available on all models).
- Intelligent battery management Maximizes battery performance, life, and reliability through intelligent, precision charging.
- Power conditioning Protects connected loads from surges, spikes, lightning, and other power disturbances.
- Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature.
- Automatic restart of loads after UPS shutdown Automatically starts up the connected equipment upon the return of utility power.
- Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be replaced.
- Disconnected battery notification Warns when a battery is not available to provide backup power.
Manageability
- Network manageable Provides remote power management of the UPS over the network.
- Audible alarms Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition.
- LED status indicators Quickly understand unit and power status with visual indicators.
- Serial connectivity Provides management of the UPS via a serial port.
- USB connectivity Provides management of the UPS via a USB port (not available on all models).
- Disconnected battery notification Warns when a battery is not available to provide backup power.
Serviceability
- User-replaceable batteries Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
- Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
- Predictive failure notification Provides early-warning fault analysis ensuring proactive component replacement.
- Resettable circuit breakers Enables a quick recovery from overload events.
- Battery failure notification Provides early-warning fault analysis on batteries enabling timely preventive maintenance
Adaptability
- Adjustable voltage-transfer points Maximizes useful battery life by widening the input voltage window or tightening the output voltage regulation.
- Adjustable voltage sensitivity Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.
Safety
- Safety-agency approved Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Technical Specifications
Output
- Output Power Capacity 1980 Watts / 2200 VA
- Max Configurable Power 1980 Watts / 2200 VA
- Nominal Output Voltage 230V
- Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage
- Output Voltage Distortion Less than 5% at full load
- Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nominal
- Topology Line Interactive
- Waveform Type Sine wave
- Output Connections
- (8) IEC 320 C13 IEC 320 C13
- (1) IEC 320 C19 IEC 320 C19
- (2) IEC Jumpers
Input
- Nominal Input Voltage 230V
- Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
- Input Connections
- IEC-320 C20
- Schuko CEE 7 / EU1-16P
- British BS1363A
- Input voltage range for main operations 160 - 286V
- Input voltage adjustable range for mains operation 151 - 302V
- Other Input Voltages 220, 240
Communications & Management
- Interface Port(s) SmartSlot
- Available SmartSlot™ Interface Quantity 1
- Control panel Multi-function LCD status and control console
- Audible Alarm Alarm when on battery : distinctive low battery alarm : configurable delays
- Emergency Power Off (EPO) Yes
Surge Protection and Filtering
- Surge energy rating 365 Joules
- Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
- Maximum Height 435.00 mm
- Maximum Width 197.00 mm
- Maximum Depth 544.00 mm
- Net Weight 48.80 KG
- Shipping Weight 61.90 KG
- Shipping Height 699.00 mm
- Shipping Width 381.00 mm
- Shipping Depth 762.00 mm
- Color Black
- Units per Pallet 9.00
Environmental
- Operating Environment 0 - 40 °C
- Operating Relative Humidity 0 - 95%
- Operating Elevation 0-3000 meters
- Storage Temperature -15 - 45 °C
- Storage Relative Humidity 0 - 95%
- Storage Elevation 0-15000 meters
- Audible noise at 1 meter from surface of unit 45.00 dBA
- Online Thermal Dissipation 275.00 BTU/hr